JDZ(X)W-35 Type Voltage Transformer |
| Applications |
JDZ(X)W-35 Type Voltage Transformer (PT for short hereinafter) is suit able for power metering,voltage monitoring and relay protection in power system with rated frequency 50Hz or 60Hz and rated voltage 35kV.
Applicable Standard:IEC60044-2 Voltage Transformer. |
| Type Designation |
|
| Operation Conditions |
Installation area:outdoor
Ambient temperature: Max. temperature 40¡æ;Min. temperature -25¡æ;Daily average temperature can't exceed 30¡æ.
Air conditions: No heavy pollution in air. |
| Technical Parameter |
|
Model |
Rated voltage radio
(kV) |
Combined accuracy or Combined accuracy classes |
Rated output
(VA) |
ltimate output
(VA) |
Rated insulation level
(kV) |
JDZW-35 |
35/0.1 |
0.2 |
60 |
1500 |
40.5/95/200 |
0.5 |
120 |
35/0.1/0.1 |
0.2/0.2 |
30/30 |
800 |
0.2/0.5 |
30/40 |
0.5/0.5 |
40/40 |
JDZXW-35 |
35/¡Ì3/0.1¡Ì3/0.1/3 |
0.2/6P(3P) |
30/100 |
800 |
40.5/95/200 |
0.5/6P(3P) |
60/100 |
35¡Ì3/0.1¡Ì3/0.1¡Ì3/0.1/3 |
0.2/0.2/6P(3P) |
20/20/100 |
400 |
0.2/0.5/6P(3P) |
20/30/100 |
0.5/0.5/6P(3P) |
30/30/100 |
|
| |
|
| Structure and Feature |
| The series PT is post type. Its hemetically sealed by epoxy resin, with design advantages of anti-pollution, anti-damp, easy to be installed is also suitable fortropic area and free from special maintenance except periodically surface clean. Secondary outlet teminal is equipped with connection teminal box. There have earth bolt at the bottom of the PT. Six holes at the bottom of the PT are suitable for mounting.There are 4 holes for mounting and grounded bolt at the bottom of this series.. |
| Outline and Mounting Dimensions |
 |
| Information Required for Order Placing |
Model.
Rated voltage radio kV.
Combined accuracy classes and Rated output VA.
Altitude m. |
|